Heat-pump Samsung VRF AM080BXMDGH/EU AM250TNBFGB/EU
VRF system (Hydro module + DVM S Eco heat pump)
Warranty: 3 years
Hydro module
Production of hot water and chilled water at low temperature.
Production of hot water up to a maximum temperature of 50 °C/80 °C (for HT models).
Two-way control: control of the leaving water temperature and of the room temperature.
Connection to low-temperature radiators and AHUs with water coils.
Production of domestic hot water.
Can be connected to DVM S heat recovery systems (except the 50 kW hydro module).
DVM S Eco heat pump
Horizontal air discharge and rear intake via one (4~5 HP) or two (8~14 HP) BLDC inverter propeller fan(s).
Each module houses one compressor: Twin rotary BLDC (4~8 HP) or inverter with Flash Injection technology (10~14 HP).
Compressor micro-frequency control in 0.01 Hz steps.
Night quiet mode available
Eurovent certified and compliant with the ErP (Ecodesign) standard.
Four-way pipe connection.
The heat pump system consists of the following components:
Outdoor unit - AM080BXMDGH/EU
Indoor unit - AM250TNBFGB/EU
Control module - MWR-WW10N
Technical specifications
Hydro module:
Power supply (Φ, #, V, Hz): 3Φ, 4, 380–415 V, 50 Hz
Heating capacity (rated): 25 kW
Power:
Heating power input (rated): 5.0 W
Heating current (rated): 7.85 A
MCA (incl. external contact): 16.1 A
MFA: 20 A
Heat exchanger: PHE
Quantity: 2 ea
Pipe size: PT 1 (25A) ø, inch
Water flow rate: 23 l/min
Flow switch: 12 l/min
Pipe connections:
Liquid pipe:
9.52 ø, mm
3/8 ø, inch
Gas pipe:
15.88 ø, mm
5/8 ø, inch
Wiring:
Power cable (L<10 m, single installation): 2.5 mm²
Transmission cable: 0.75~1.50 mm²
Refrigerant: R134A (Fluorinated greenhouse gas, GWP=1.430)
Control method: EEV
Factory charge: 2.15/3.07 kg/t CO₂e
Sound:
Sound pressure: 42 dB(A)
Sound power: 60 dB(A)
Weight: 103.5 kg
Dimensions (W x H x D): 518 x 1210 x 330 mm
Operating temperature range:
Ambient:
Heating: –20~43 °C
Hot water (cooling main, HR): –20~43 °C
Leaving water Heating: 25~80 °C
DVM S Eco outdoor unit:
Power supply (Φ, #, V, Hz): 3Φ, 380~415 V, 50 Hz
Performance:
HP: 8 HP
Capacity:
Cooling: 22.4 kW
Heating: 22.4 kW
Maximum number of indoor units that can be connected: 13 EA
Total capacity of connected indoor units:
Min.:11.2 kW
Max.: 29.1 kW
Power:
Power input:
Cooling: 10.98 W
Heating: 6.4 W
Current:
Cooling: 17.2 A
Heating: 10 A
Current:
Minimum SSC value: 3.4 MVA
MCA: 16.1 A
MFA: 20 A
Energy efficiency:
EER (rated, cooling): 2.04 W/W
COP (rated, heating): 3.5 W/W
SEER (cassette): 6 W/W
SCOP (cassette): 4.25 W/W
Compressor: BLDC twin rotary
Output: 4.78 x 1 kW × n
Oil: PVE
Initial charge: 1700 cu. cm
Fan:
Type and air direction:
Axial
Horizontal
Number of fans: 2 EA
Air flow rate: 135 m³/min
External static pressure (Max.):
3 mmAq
29.4 Pa
Fan motor: BLDC motor
Output x quantity: 139 x 2 W
Pipe connections:
Liquid pipe:
9.52 ø, mm
3/8 ø, inch
Gas pipe:
19.05 ø, mm
3/4 ø, inch
Pipe length (outdoor/indoor unit) Max. (Eq.): 100 (130) m
Pipe length (1st branch to indoor unit) Max.: 40 m
Total pipe length (system) Max.: 300 m
Height difference (outdoor unit in the highest position) Max.: 30 m
Height difference (indoor unit in the highest position) Max.: 30 m
Height difference (indoor unit/indoor unit) Max.: 30 m
Cable connections:
Communication:
Min.: 0.75 mm²
Note: F1, F2
Refrigerant: R410A (Fluorinated greenhouse gas, GWP=2.088)
Factory charge: 3.70/7.73 kg/t CO₂e
Sound:
Sound pressure:
Cooling: 58 dB(A)
Heating: 59 dB(A)
Sound power: 73 dB(A)
Weight: 115 kg
Dimensions (W x H x D): 940 x 1420 x 330 mm
Operating temperature range:
Cooling: –5.0~48.0 °C
Heating: –20.0~24.0 °C
-
Manufacturer:
-
Refrigerant:R410A
-
Power supply:Three-phase